Standards: Pressure relief devices in gas/vapor service.

§ 65.111 Standards: Pressure relief devices in gas/vapor service.

(a) Compliance schedule. The owner or operator shall comply with this section no later than the implementation date specified in § 65.1(f).

(b) Compliance standard. Except during pressure releases as provided for in paragraph (c) of this section, each pressure relief device in gas/vapor service shall be operated with an instrument reading of less than 500 parts per million as measured by the method specified in § 65.104(b) and (c).

(c) Pressure relief requirements. (1) After each pressure release, the pressure relief device shall be returned to a condition indicated by an instrument reading of less than 500 parts per million, as soon as practical, but no later than 5 calendar days after each pressure release except as provided in § 65.105(d).