New source performance standards (NSPS).

§ 423.15 New source performance standards (NSPS).

(a) 1982 NSPS. Any new source as of November 19, 1982, subject to paragraph (a) of this section, must achieve the following new source performance standards, in addition to the limitations in § 423.13 of this part, established on November 3, 2015. In the case of conflict, the more stringent requirements apply:

(1) pH. The pH of all discharges, except once through cooling water, shall be within the range of 6.0-9.0.

(2) PCBs. There shall be no discharge of polychlorinated biphenyl compounds such as those commonly used for transformer fluid.

(3) Low volume waste sources, FGD wastewater, flue gas mercury control wastewater, combustion residual leachate, and gasification wastewater. The quantity of pollutants discharged in low volume waste sources, FGD wastewater, flue gas mercury control wastewater, combustion residual leachate, and gasification wastewater shall not exceed the quantity determined by multiplying the flow of low volume waste sources times the concentration listed in the following table:

Pollutant or pollutant property NSPS
Maximum for any 1 day (mg/l) Average of daily
values for 30
consecutive days
shall not exceed
(mg/l)
TSS100.030.0
Oil and grease20.015.0

(4) Chemical metal cleaning wastes. The quantity of pollutants discharged in chemical metal cleaning wastes shall not exceed the quantity determined by multiplying the flow of chemical metal cleaning wastes times the concentration listed in the following table:

Pollutant or pollutant property NSPS
Maximum for
any 1 day
(mg/l)
Average of daily
values for 30
consecutive days
shall not exceed
(mg/l)
TSS100.030.0
Oil and grease20.015.0
Copper, total1.01.0
Iron, total1.01.0

(5) [Reserved]

(6) Bottom ash transport water. The quantity of pollutants discharged in bottom ash transport water shall not exceed the quantity determined by multiplying the flow of the bottom ash transport water times the concentration listed in the following table:

Pollutant or pollutant property NSPS
Maximum for
any 1 day
(mg/l)
Average of daily
values for 30
consecutive days
shall not exceed
(mg/l)
TSS100.030.0
Oil and grease20.015.0

(7) Fly ash transport water. There shall be no discharge of pollutants in fly ash transport water.

(8)

(i) Once through cooling water. For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table:

Pollutant or pollutant property NSPS
Maximum concentrations
(mg/l)
Total residual chlorine0.20

(ii) Total residual chlorine may only be discharged from any single generating unit for more than two hours per day when the discharger demonstrates to the permitting authority that discharge for more than two hours is required for macroinvertebrate control. Simultaneous multi-unit chlorination is permitted.

(9)

(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: